Sample Chart
Onset “HOBO data Temperature/Humidity Data Logger logger.
Interval:
Six Months
Task:
Verify reasonable operation of the store room Data Logger
Tools:
Onset HOBOWare software installed and configured on a P.C.
Access to current Temperature and humidity as reported by the ATIS:
Procedure:
Observe the Data Logger display, assure that the battery Monitor is normal.
Assure that the memory Remaining more than 50%.
Remove the DataLogger from the Store room and place it outside, over grass, in a shaded area for 1.5 hours hour.
During the test period, obtail current Temp/humitiy from the airport ATIS.
after the Test period, download the Data logger.
Compare the Temperature and Humidity from the official information to the Data logger.
print and save the results.
Record the results on the Data Tag.
Replace the battery as required.
Erase the memory.
Reinstall the data logger.
Reset the CAFAM Inspection NEXT DUE.
END